POWER QUALITY ANALYSER RPM100/RPM100C

Created on 10.22
RPM100/RPM100C
panel mounting quality analyser according IEC 61000-4-30 class A
0
I can give fault log report as follow:
  • Phase sequence
  • Phase fault
  • Voltage over
  • Voltage under
  • Voltage transient
  • Voltage sag/swell
  • Frequency over
  • Current over (load)
  • Leakage
  • Short circuit
  • Voltage harmonic
  • Current harmonic
General features
The power quality analyzer RPM100/RPM100C is a high-end power quality analyzer, able to monitor and record the major power quality parameters. It provides an accurate measurement, voltage characteristics are monitoring according to EN61000-4-30:2015 Ed.3 Class A specification.
RPM100/RPM100C is designed to measurement of electrical parameters in LV and MV systems. It is built on 32bit DSP processor that it can provide sufficient processing capabilities for real-time measurement and calculation of all parameters. Continuous sampling of the voltage and current inputs at 66.5 KHz, guarantees the highest accuracy. At the same time it acts as event/fault recorder, capable to store a high number of voltage events and disturbances, frequency variations, inrush current. Extra current measurement channels give the possibility to monitor earth leakage current. RPM100C is provided with a correction function for CT wiring errors.
The RPM100/RPM100C is the ideal instrument for power quality monitoring according to EN50160 of the incoming energy supplyside as well as on the consumer side in order to find and analysis the root cause of network problems.
Benefits
Ÿ 5 current measurement channels in comparison with
other standard three-phase devices.
Ÿ Current inputs of current transformer to grant an
accurate current measurement.
Ÿ Continuous monitoring of the power quality.
Ÿ Several possibilities for instrument data transmission:
RS-485, Ethernet with Modbus RTU/TCP,LoRa,WIFI
Application
Ÿ Power monitoring & control systems
Ÿ Switchboards, gensets, motor control, etc
Ÿ Individual machine load monitoring
Ÿ Power demand analysis and management
Ÿ Harmonics monitoring
Ÿ Leakage monitoring
Ÿ Short circuit warning
Main features
Main features
Ÿ Measurements: VL-L, VL-N, I, In, Iz, Cos∅, Pf, total Pf, Hz, W,
∑W, Va, ∑Va, Var, ∑Var, Kwh, Kvarh, V-THD, I-THD, 1-128th
harmonic , system running hours, % voltage unbalance, %
system load, % system leakage, frequency; fast simultaneous
sampling on all 8 channels at 1024 samples/cycle(True RMS
measurements) For single-phase, two-phase, three-phase system
Ÿ 4 voltage channel input, voltage direct connection up to 690VLL or
through PT for MV and HV systems.
Ÿ 5 current input: 0.05-5.5A
Ÿ 4th current channel dedicated for neutral current
measurements, the current measuring range (CT primary and
secondary ) can be programmed together with the main three-phase
channels
Ÿ 5th current channel reserved for Earth Leackage monitoring
(ZCT input) according to IEC60755 & IEC61140 Suitable for
45-65Hz systems
Ÿ All measured voltage characteristics certified according to
IEC/EN61000-4-30:2015 Ed.3, Class A
Ÿ 4 quadrants energy measurement support bi-directional
power monitoring includes measurement on regenerative
loads, also monthly energy calculation
Ÿ Transients detection >25us, Detection of events >10ms
Ÿ Voltage flicker measurement, and waveform capture
Ÿ Maximum, minimum and demand for U, I, P, Q, S in
hours, days, months
Ÿ Phase diagram for voltage, current
Ÿ Detects CT wiring errors
Data storage & recordings
Ÿ Voltage and current sag/swell and transient event capture
Ÿ Waveform acquisition and capture of voltage and current
Ÿ Automatic fault analysis and report: Phase sequence, Phase
fault, Voltage over, Voltage under, Sag/swell, Frequency over,
Current over, Short circuit, Leakage,Voltage harmonic,
Current harmonic(according to IEC62606: 2013)
Ÿ Alarm event log: VL-L, VL-N, I, In, ΣW, ΣVar, THD-U, THD-I...
Ÿ Monthly electricity statistics
Ÿ Built in 256M flash memory &32MB RAM for event and
transient memory
Ÿ Micro SD(support 32GB) for fault logger and data logger
Ÿ Data recorded in standard excel file formats for further
EN50160 analysis
Clock & language
Function module (only one can be selected)
Ÿ Real time clock with integrated backup rechargeable
battery
Ÿ English, Chinese (traditional & simplied) or other
Communication
Ÿ RS485 port of Modbus RTU
Ÿ Ethernet port of Modbus TCP/IP+web server
Ÿ 7 digital input+2 relay output (remote or alarm) (Standard)
Ÿ 7 digital input+2 analog output (4-20mA) for V1, V2, V3, V12, V23, V31, I1, I2, I3
Ÿ Ethernet (Modbus TCP), web server+2 digital input+2relay output (remote or alarm)
Ÿ LoRa wireless (Private protocol)+2 digital input+2 relay output (remote or alarm)
Ÿ RS-485 interface (Modbus RTU)+2 digital input+2 relay output (remote or alarm)
Ÿ WIFI wireless+2 digital input+2 relay output (remote or alarm)
Order
Model
Description
RPM100.E (TFT LCD)
RPM100.E ((Color TFT LCD)
Ethernet (Modbus TCP),web server +2 digital input +2 relay output (Standard)
RPM100.A
RPM100C.A
7 digital input +2 analog output(4-20mA)
RPM100.I
RPM100C.I
7 digital input +2 relay output(remote or alarm)
RPM100.L
RPM100C.L
LoRa (private protocol)+2 digital input +2 relay output(remote or alarm)
RPM100.R
RPM100C.R
RS-485(Modbus RTU)+2 digital input +2 relay output(remote or alarm)
RPM100.W
RPM100C.W
WIFI wireless+2 digital input +2 relay output
RPM100.D
RPM100C.D
Auxiliary supply: 12...48VDC
Note: RPM100C’s LCD display is a 3.5 inch color TFT LCD and RPM100C has multi-tariffe energy measurement.
Mechanical dimensions
0
Auxiliary supply
Operating voltage (Un)
85···265 VAC 50/60Hz 10W / 110-330VDC/24-48VDC(depend on order)
Power consumption
10VA max
Measurement input
Voltage inputs for direct connection:
Phase-neutral(L-N): max 400V RMS CAT III
Input impedance(for direct voltage inputs):
>4MΩ
CT inputs:
max 5.5A RMS
CT inputs overload capacity :
max 10A
CT inputs Self-consumption :
<0.2VA
Accuracy
Three phase voltage:
±0.2%
Currents:
±0.2%
Powers:
±0.3%
Powers factor:
±0.3%
Frequency:
±0.02%
Harmonics:
Class 1 (IEC/EN61000-4-7)
Active energy:
Class 0.2S (IEC/EN 62053-22)
Reactive energy:
Class 0.5S (IEC/EN 62053-23)
Insulation
Insulation voltage
3kV for 1 min., 50Hz
Display
Display type
3.2inch 240x160 pix LCD/3.5 inch 320x240 color TFT LCD
I/O
Digital inputs:
Active dry contact
Digital outputs:
2 Relay N/O 220VAC 5A
Analog outputs:
4-20mADC / max load 500Ω
Pulse output:
5-30VDC Max.50mA, Min. 50msec pulse width
Memory
System memory:
256 MB Flash, 32MB RAM
Recording memory:
max 32 GB SD (TF)
Communication
Ethernet port:
Auto MDIX Rj45 10/100 Base Ethernet
RS-485 port:
1 optoisolated, 4800-57600
Protocols:
HTTP, HTTPS, Modbus RTU/TCP
Environmental conditions
Opterating temperature:
-10···+55°C
Storage temperature:
-25···+75°C
Relative humidity:
95% max without condensing
Altitude:
max 2000m AMSL
Installation & use:
Internal
Mechanical characteristics
Mounting:
Panel mount 96x96mm(The panel cut-size 92*92mm)
Size:
Front(WXH)96x96mm, Rear (HxD) 90x70mm
Degree of protection:
IP40(optional IP54) on front, IP20 housing and terminals
Weight:
450g
Standard compliance
Reference standard:
IEC61010-1; IEC61557-1;IEC61557-12; IEC61326-1;IEC62053-21;
IEC62053-22; IEC62053-31; IEC60068-2-1; IEC60068-2-30;
IEC60364-5-52; IEC61000-3-2; IEC61000-3-3; IEC61000-4-2;
IEC61000-4-3; IEC61000-4-4; IEC61000-4-5; IEC61000-4-6;
IEC61000-4-8; IEC61000-4-11; IEC61000-4-30