RDR-1D IDMT EARTH FAULT RELAY DRAW OUT WITH SELF CT SHORTING RDR series relay have been designed for controlling, protecting and monitoring industrial, utility distribution networks and substations. They can also be used as part of a protection scheme for feeders, transformers and generators. |
50/60 Hz
|
|
Protection features
| Control
(Trip Circuit supervision, reset, trip) |
Time current curves
| Measurements
Power supply ratings
|
Software
| Mounting
|
Earth fault protection (50N/51N) The independent two stages are available for earth fault protection. For first stage (Ie>) the user can select definite time delay or inverse time delay with different type of curves. The second Hi-Set stage can be configured with definite time only. |
Harmonic blocking (50H) Harmonic block detects high inrush current inflows that occurs upon connection of transformers or rotating machines. The function will block the phase over-current and earth fault elements. |
Circuit breaker failure protection (50 BF) The CB Failure Protection is based on supervision of phase and earth currents after tripping events. The test criterion is whether all phase currents have dropped to less than 5% of In within tCBFP. If one or more of the phase currents have not dropped to specified current within this time, CB failure is detected and the assigned output relay is activated. |
Trip circuit supervision (74TC) This feature continuously supervises trip circuit of both pre closing and post closing conditions in circuit breaker. It detects tripping mechanism failure like circuit breakage contact degeneration in wires, contacts and coils. Note: Trip counter is incremented on the basis of getting trip command from relay and not on the basis of external mechanism (circuit breaker) operation. |
Programmable Input Quantities |
|
n: Rated primary current of phase Cts | 1-10000A step 1A |
Secondary current of phase Cts | 1/5A |
Fr: System frequency | 50/60Hz |
50N/51N(I0>): First earth fault element |
|
Function enabling | ON/OFF |
Current pick-up range | 80-100%xIp (0.8-1xIp) step 1% |
Current setting range | 20-300%xIp (0.2-3xIp) step 1% |
Definite trip time delay(10x[Ie>]) in inverse time operation modes | 0.02-1.5x trip time delay (10x[Ie>]) step 0.01 0.02-260Sec (curves: DTL) |
Output delay (TR) | 30ms |
Time current curves | IEC A / IEC B / IEC C / IEEE MI / LI / DTL |
50N/51N(I0>>): Second earth fault element |
|
Function enabling | ON/OFF |
Current setting range | 50-1000%xIp (0.5-10xIp) step 1 |
Trip time | 0.02-60s step 0.01 |
Output delay (TR) | 30ms |
Typical characteristics |
|
Accuracy at reference value of influencing factors | ±0.5-1% for measurements |
Rated current | 1A/5A |
Current overload | 400A for 1 sec; 2.5xIn continuous |
Burden on current input | 0.2VA a In = 1A; 0.4VA a In = 5A |
Average power supply consumption | ≤10VA |
Output relays | 6 A; Vn = 250 V |
A.C. resistive switching = 1500W (400V max) |
|
make = 30 A (peak) 0.5 sec.; |
|
break = 0.3 A, 110 Vcc, |
|
L/R = 40 ms (100,000 op.) |
|